Model AM050FNKDEH/EU AM100FNKDEH/EU Power Supply Φ, #, V, Hz 1Φ, 2, 220~240 V, 50 Hz 1Φ, 2, 220~240 V, 50 Hz Performance Temp. Exchange Effi ciency Cooling Turbo/High/Low % 70/70/74 70/70/74 Heating Turbo/High/Low % 75/75/79 75/75/79 Effective Enthalpy Exchange Effi ciency Cooling Turbo/High/Low % 60/60/66 62/62/68 Heating Turbo/High/Low % 73/73/79 75/75/81 Outside Air Processing Capacity Cooling (DX Coil/Element) - 5.1 (3.6/1.5) 10.5 (7.1/3.4) Heating (DX Coil/Element) - 6.5 (4.0/2.5) 13.2 (8.0/5.2) Fan Airfl ow Rate Turbo/High/Low (UL) m3/hr 500/500/360 1,000/1,000/690 l/s 138.9/138.9/100.0 277.8/277.8/191.7 External Static Pressure Turbo/High/Low mmAq 16.30/10.20/8.70 15.30/9.20/7.60 Pa 160.00/100.00/85.00 150.00/90.00/75.00 Motor Type - BLDC BLDC Output W 60 70 Quantity ea 2 2 Power Power Input Turbo/High/Low W 220/140/90 510/350/235 Current Input Turbo/High/Low A 1.7/1.0/0.6 3.7/2.4/1.6 Piping Connections Liquid Pipe ø, mm 6.35 6.35 ø, inch 1/4 1/4 Gas Pipe ø, mm 12.70 12.70 ø, inch 1/2 1/2 Drain Pipe ø, mm VP25 (OD 32, ID 25) VP25 (OD 32, ID 25) ø, inch VP25 (OD 1-1/4”, ID 1”) VP25 (OD 1-1/4”, ID 1”) Water Supply ø, mm 12.70 12.70 ø, inch 1/2 1/2 Field Wiring Power Source Wire mm² 1.5/2.5 1.5/2.5 Transmission Cable mm² 0.75~1.50 0.75~1.50 Refrigerant Type - R410A(Fluorinated greenhouse gas, GWP=2,088) Control Method - EEV EEV Sound Sound Pressure1 Turbo/High/Low dB(A) 36/32/28 36/33/31 Sound Power dB(A) 67 67 Dimensions Net Weight kg 61.0 90.0 Net Dimensions (W x H x D) mm 1,553 x 270 x 1,000 1,763 x 340 x 1,135 Supply/Return/Exhaust/Outside Duct Flange (ø) mm 200 250 Ambient Conditions Around Unit - 0~40 °C DB, 80 % RH or less 0~40 °C DB, 80 % RH or less Outdoor Air - -15~40 °C DB, 80 % RH or less -15~40 °C DB, 80 % RH or less Return Air - 0~40 °C DB, 80 % RH or less 0~40 °C DB, 80 % RH or less Air Filter - Pre fi lter Pre fi lter Accessories Differential pressure switch² Wired Remote Controller CO₂ Sensor MOS-P1050 MWR-WG00*N MOS-C1 1 Sound level was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. 2 Please order MOS-P1050 separately. Differential pressure switch (model code: MOS-Pa) is a mandatory accessory for all ERV and ERV Plus units in EU countries according to Ecodesign Directive 1253/2014. • Energy recovery ventilation unit with built-in direct expansion coil. • Cellulose heat exchanger element. • High Effi ciency (F7 class) air fi lter. • Two centrifugal fans direct driven by electric BLDC motor. • Optional CO₂ sensor for automatic regulation. • Bypass operation mode when there’s a small temperature difference between indoor and outdoor environment (automatically or manually operated). • Frost formation prevention without electric heater. • Auto Restart function. Specifications ERV Plus for DVM S 234