Model AM180JNHFKH/EU AM224JNHFKH/EU AM220FNHDEH/EU Power Supply Ф, #, V, Hz 1Ф, 2, 220–240 V, 50 Hz 1Ф, 2, 220–240 V, 50 Hz 1Ф, 2, 220–240 V, 50 Hz Performance Capacity (Nominal) Cooling kW 18.0 22.4 22.4 Heating kW 20.0 25.0 25.0 Power Power Input (Nominal) Cooling W 340 530 530 Heating W 340 530 530 Current Input (Nominal) Cooling A 1.90 2,9 3.80 Heating A 1.90 2,9 3.80 Current Input (Nominal) MCA A 5.72 - 5.80 MFA/MOP A 15 - 15 Fan Type - Sirocco Fan Sirocco Fan Sirocco Fan Number of Fans ea 1 1 1 Airflow Rate H/M/L (UL) m³/min 58.0 / 50.0 / 43.0 72.0 /61.0 / 50.0 58.0 / 52.0 / 47.0 l/s 966.67/833.33/716.67 1200.00/1016.67/833.33 966.67/866.67/783.33 External Static Pressure Min/Std/Max mmAq 5.00/7.34/20.00 5.00/7.34/20.00 5.00/15.00/25.00 Pa 49.00/71.93/196.00 49.03/71.93/196.00 49.03/147.10/245.17 Fan Motor Model - - - - Output x n W 630 x 1 630 x 1 400 x 1 Piping Connections Liquid Pipe Ø, mm 9.52 9.52 9.52 Ø, inch 3/8 3/8 3/8 Gas Pipe Ø, mm 19.05 19.05 19.05 Ø, inch 3/4 3/4 3/4 Drain Pipe Ø, mm VP25 (OD 25, ID 20) VP25 (OD 25, ID 20) VP25 (OD 32, ID 25) Field Wiring Power Source Wire Below 20 m/ over 20 m mm² 1.5/2.5 1.5/2.5 1.5/2.5 Transmission Cable Transmission Cable mm² 0.75~1.50 0.75~1.50 0.75~1.50 Remark - F1,F2 F1,F2 F1,F2 Refrigerant Type - R410A (Fluorinated greenhouse gas, GWP=2,088) Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED Sound² Sound Pressure1 (H/M/L) dB(A) 43/39/35 44/40/36 45/43/41 Sound Power Cooling dB(A) 80 81 Dimensions Net Weight kg 82.5 82.5 89.0 Net Dimensions (W x H x D) mm 1350 x 450 x 910 1350 x 450 x 910 1240 x 470 x 1,040 Air Filter - - - Additional Accessories Drain Pump Internal - MDP-G075SQ MDP-G075SQ MDP-N047SNC1D External - MDP-G075SP MDP-G075SP - Max. Lifting Height/ Displacement mm / litres/h - - 750/24 • Two-position field adjustable air return, on the bottom or at the rear of the unit. • Equipped with two Sirocco fans direct driven by a single motor. • Long-life HD 40 permanent filter is included (model-specific). • Can be controlled by Smartphone via Wi-Fi Kit (Optional). • Auto Restart function. • Auto ESP setting (model-specific). HSP Duct (R410A) Specifications * Universal indoor units, universal controller and universal accessories can be installed both with DVM R410A and DVM R32 Outdoor units. 1 Sound pressure level is obtained in an anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. Sound pressure level may differ depending on operation conditions. 122