Model (HE) AM160FNBDEH/EU AM320FNBDEH/EU AM500FNBDEH/EU Power Supply Ф, #, V, Hz 1Ф, 2, 220–240 V, 50 Hz 1Ф, 2, 220–240 V, 50 Hz 1Ф, 2, 220–240 V, 50 Hz Performance Capacity (Nominal) Cooling1 kW 14.0 28,0 44.8 Heating2 kW 16.0 31.5 50.4 Power Power Input (Nominal) Cooling W 10 10 10 Heating W 10 10 10 Current Input (Nominal) Cooling A 0,05 0,05 0,05 Heating A 0,05 0,05 0,05 MCA (Including External Contact) A 2.2 2.2 2.2 MFA A 2,75 2,75 2,75 Heat Exchanger Type - PHE PHE PHE Quantity ea 1 1 1 Pipe Size Ø, inch PT 1 (25A) PT 1 (25A) PT 1 1/4 (32A) Water Flow Rate l/min 48 92 150 Piping Connections Liquid Pipe Ø, mm 9,52 9,52 12,70 Ø, inch 3/8 3/8 1/2 Gas Pipe Ø, mm 15,88 22,20 28,58 Ø, inch 5/8 7/8 1 1/8 Field Wiring Power Source Wire (L<10 m, Single Installation) mm² 2.5 2.5 2.5 Transmission Cable mm² 0,75~1,50 0,75~1,50 0,75~1,50 Refrigerant Type - R410A (Fluorinated greenhouse gas, GWP=2,088) Control Method - EEV EEV EEV Sound Sound Pressure3 dB(A) 27 28 31 Dimensions Net Weight kg 29.0 33.0 40.0 Net Dimensions (W × H × D) mm 518 x 627 x 330 518 x 627 x 330 518 x 627 x 330 Operating Temperature Range Ambient Cooling °C +15 ~ 48 +15 ~ 48 +15 ~ 48 Heating °C -20.0~35.0 -20.0~35.0 -20.0~35.0 Hot Water (Main Cooling, HR) °C -20.0~35.0 (43.0) -20.0~35.0 (43.0) -20.0~35.0 (43.0) Leaving Water Cooling °C 5.0~30.0 5.0~30.0 5.0~30.0 Heating °C 20.0~50.0 20.0~50.0 20.0~50.0 • Production of low temperature hot water and chilled water. • Hot water production to a maximum temperature of 50°C (80°C for HT models). • Two-way control: leaving water temperature and room temperature control. • Connection to low temperature radiators and AHU water coils. • Hot water production for domestic hot water use. • Connectable to Heat Recovery DVM S systems (excluding 50 kW hydro unit). Controls Wired Remote Controller Wired Remote Controller Wi-Fi Kit (optional) MWR-WW00N MWR-WW10*N MIM-H04EN Specifications may be subject to change without prior notice for product improvement. 1 Nominal cooling capacities are based on; - Water temperature: 23°C inlet, 18°C outlet - Indoor temperature: 27°C DB, 19°C WB - Outdoor temperature: 35°C DB, 24°C WB 2 Nominal heating capacities are based on; - Water temperature: 30°C inlet, 35°C outlet - Indoor temperature: 20°C DB - Outdoor temperature: 7°C DB, 6°C WB 3 Sound pressure level is obtained in an anechoic room. Sound pressure level is a relative value, depending on the distance and acoustic environment. Sound pressure level may differ depending on operation conditions. Specifications DVM Hydro Unit 202